Control your Nibe (KNV) Heatpump with Loxone

HomeTechnical news
Book now!

Control your Nibe (KNV) Heatpump with Loxone

The choice of paring Nibe Heatpumps with Loxone offers the possibility of:
  • integrating demand-based heating and cooling depending on e.g. presence or the protection of open windows
  • Interaction with the blinds for saving effects by passive cooling thanks to Loxone automatic shading
  • Active integration in interaction with e.g. PV- systems in a Loxone Energy Management
  • Using flexible electricity tariffs with the Spot Price Optimizer.
  • Use statistics ore individual notifications
  • Create your own individual schematics
  • Reduce cycles and operating hours of your Nibe Heatpump
  • Create e.g. yearly operation goals like certain annual runtime forces for hybrid systems e.g. (Heatpump 60% amount of energy, Gas heater 40% amount of energy) to fulfill the requirements of your local government.
  • Grid management according to §14a ENWG in Germany
  • In addition to the electrical power, the current and total thermal energy can also be visualized via the Loxone Energy Flow Monitor. To the compact overview for e.g. contractors.
  • Influence on the hot water circulation pump by controlling via the presence detectors.
  • Increased security through leakage detection or activation of IP cameras in the plant room.

_________________________________________________________________________________________________
Please note: The LAN cable is connected to the controller for the air/water heat pump and to the Touch control module for the brine/water heat pump



UseCase: Integration of a Nibe Topline S1156:

  • Commercial building with heating, cooling, heat buffer, warm water storage and heating circuit.
  • Device Brine/Water Topline S1156
  • Heating/Cooling buffer tank
  • Warm water storage tank --> Controlled by Loxone
  • Mixing circuit heating/cooling HC1 (e.g. ceiling heating/cooling) --> Controlled by Loxone

Inputs :

  • Actual Outdoor temperature [BT1]
  • Actual Hot Water Bottom temperature [BT6]
  • Acutal Supply Flowtemperature HC1 [BT2]
  • State Room temperature HC1 [BT50]
  • State Offset Curve HC1
  • State Heat Curve HC1 [BT50]
  • Total Thermal Power Heating
  • Total Operating time direct heater
  • Actual Return temperature HC1 [BT3]
  • Actual Brine Out Flowtemperature [BT11]
  • Actual Brine In Flowtemperature [BT10]
  • State Compressor
  • Actual Hot Water Top temperature [BT7]
  • Total Thermal Power Hot Water
  • Actual Heatpump Flowtemperature [BT12]
  • Actual Liquid Line temperature [BT15]
  • Actual Outdoortemperature [BT1]
  • Actual Heatpump Flow Sensor [BF1]
  • State Brine Pump Speed [GP2]
  • State Compressor Starts
  • State Circulation pump HC1 [GP10]
  • State Calculated Supply Flowtemperature
  • Actual Electrical Power Compressor
  • State Compressor Operation hours
  • State Hot Water Demand
  • State Hot Water operation mode
  • State Cooling operation mode
  • State Heatpump Operating prioritisation
  • Actual Flowtemperature Buffer to HC [BT25]
  • State Circulationpump HC1
  • Actual Current BE3
  • Actual Current BE2
  • Actual Current BE1
  • State Heatpump Operating mode
  • Actual Electrical Power
  • State Hot Water Circulation pump [GP11]
  • State Target Heating Supply Flowtemperature HC1
  • State Target Cooling Supply Flowtemperature HC1
  • State Alarm number
  • State Active alarm
Automation system for a rental room or Airbnb room
Previous article
Automation system for a rental room or Airbnb room
How much do you know about heat pumps?
Next article
How much do you know about heat pumps?

Contact Us

  • phone

    Call Us
    + 30 2102620025

  • location

    Leoforos Thessalonikis 65,
    Nea Filadelfia, Athens.

Greek Ελληνικά English English

Shop

  • Service plans
  • Offers

Information

  • Γ.Ε.Μ.Η. 139224002000
  • Customer satisfaction survey
  • Terms of use website
  • Service contracts terms
  • Shipping terms
  • Payment options
  • Terms of use eshop
  • Jobs
  • Direct payment
  • Contact us

Newsletter

Subscribe now!

Un-subscribe

Invalid e-mail address
 
Please wait...

Copyright © KtirioService 2006-2025. All Right Reserved.
Designed & developed by webgift.